OpenFOAM-based data-center cooling and hotspot analysis workflow
ThermoFOAM-DC is a reproducible OpenFOAM workflow for studying simplified air-cooled data-center thermal management. Version 0.1 models a rectangular data-center room with rack heat-source zones, floor supply tiles, a return outlet, buoyancy-driven thermal transport, and RANS turbulence modelling.
This v0.1 release adopts RNG k-epsilon as the primary turbulence model, selected from the grid-sensitivity and y+ verification study. Standard k-epsilon and k-omega SST setups are retained as sensitivity cases to compare the effect of turbulence-model choice on the cooling predictions.
Included in this release:
- 3D simplified data-center room geometry
- six rack heat-source zones using
fvModels - floor-mounted cold-air supply tiles
- return outlet
foamRun -solver fluidworkflow for OpenFOAM Foundation v13 / openfoam-dev style cases- RNG k-epsilon primary baseline case
- uniform structured grid study:
grid_07,grid_10,grid_14 - late-iteration averaging for quasi-steady oscillatory RANS results
- y+ verification for wall-function consistency
- standard k-epsilon and k-omega SST sensitivity setups
- non-uniform mesh-layout sensitivity resources
- custom
dcMetricsPluspost-processing utility - curated result tables and plots
Deferred to v0.2:
- low/high supply velocity cases
- warmer supply air case
- high rack heat-load case
- overloaded rack case
- design trade-off plots and ranking
The v0.1 model uses a single fluid region representing room air. Racks are represented as heat-source cell zones rather than detailed solid cabinets. This is a deliberate baseline simplification.
Main physics:
- turbulent room airflow
- temperature transport
- buoyancy through Boussinesq thermodynamics
- rack heat sources
- wall-function RANS turbulence modelling
Primary turbulence model:
RNGkEpsilon
Sensitivity models:
kEpsilon
kOmegaSST
The steady RANS solutions show noticeable quasi-steady oscillation in monitored thermal metrics. Therefore, v0.1 reports late-iteration averaged metrics over:
4000, 5000, 6000, 7000, 8000
The final value at 8000 is treated as a supporting snapshot, not as divine truth. This is a CFD project, not a fortune cookie.
The custom dcMetricsPlus utility extracts:
- average rack-inlet temperature
- 95th percentile rack-inlet temperature
- maximum rack-inlet temperature
- rack-inlet risk fraction above 305 K
- average room temperature
- 95th percentile room temperature
- maximum room temperature
- room hotspot fraction above 315 K
- return outlet area-average temperature
- return outlet outflow-weighted temperature
- return outlet outflow flux
- pressure difference between supply and return
For grid independence, integrated/statistical quantities such as TavgRackInlet, T95RackInlet, T95Room, and hotspot fractions are emphasized over single-cell maxima.
The formal grid study uses the uniform structured grid family and late-iteration averages from 4000-8000.
| Grid | Cells | hEff [m] | TavgRackInlet mean [K] | T95RackInlet mean [K] | Rack risk fraction T>305K | TavgRoom mean [K] | T95Room mean [K] | Room hotspot fraction T>315K | deltaP mean [Pa] | Role |
|---|---|---|---|---|---|---|---|---|---|---|
| grid_07 | 38,220 | 0.1401 | 302.957 | 313.911 | 0.497 | 307.129 | 314.169 | 0.0319 | 0.598 | coarse reference |
| grid_10 | 105,000 | 0.1000 | 302.695 | 313.542 | 0.481 | 307.123 | 313.513 | 0.0161 | 0.566 | production mesh candidate |
| grid_14 | 285,180 | 0.0717 | 302.040 | 311.928 | 0.449 | 306.728 | 312.944 | 0.00914 | 0.583 | fine-grid reference |
The fine grid was checked further because the minimum y+ was locally below 30. Only 8 out of 26,763 wall faces were below y+ = 30, corresponding to 0.0299% of wall faces. Therefore, the fine grid is acceptable as the reference grid for wall-function RANS.
| Patch | Faces | Faces with y+ < 30 | Percent below 30 | Min y+ | Avg y+ | Max y+ |
|---|---|---|---|---|---|---|
| floor | 6526 | 0 | 0.0000% | 32.1298 | 91.7744 | 160.0916 |
| ceiling | 6209 | 2 | 0.0322% | 27.4215 | 116.0299 | 183.3349 |
| walls | 14028 | 6 | 0.0428% | 27.4215 | 89.9197 | 266.7922 |
| total | 26763 | 8 | 0.0299% | - | - | - |
grid_07: coarse referencegrid_10: practical production mesh candidate with low runtimegrid_14: fine-grid reference with acceptable y+ distribution
For v0.2 parameter studies, use grid_10 for the full sweep and rerun selected important cases on grid_14 for verification.
From the repository root:
cd cases/01_baseline_RNGkEpsilon
./Allclean
./AllrunCompile the post-processing utility:
cd ../../src/dcMetricsPlus
wmakeRun metrics:
cd ../../cases/01_baseline_RNGkEpsilon
dcMetricsPlusRun y+ verification:
foamPostProcess -solver fluid -func yPlus -latestTime
python3 ../../scripts/yplus_fraction.py 8000/yPlus 30
=======
# ThermoFOAM-DC v0.2
**OpenFOAM-based data-center cooling, hotspot, and parameter-study workflow**
ThermoFOAM-DC is a reproducible OpenFOAM workflow for studying simplified air-cooled data-center thermal management. Version 0.2 extends the verified v0.1 RNG k-epsilon baseline into a ten-case cooling parameter study covering supply velocity, supply temperature, rack heat load, overloaded-rack scenarios, pressure-flow proxy metrics, per-rack hotspot analysis, and CFD visualization outputs.
This repository is intended as an open engineering benchmark and research workflow, not a production-certified data-center digital twin.
---
## Version history
- **v0.1.0**: Baseline OpenFOAM data-center cooling workflow with grid sensitivity, y+ verification, turbulence-model sensitivity, and custom hotspot metrics.
- **v0.2.0**: Ten-case parametric cooling study with automated global/per-rack post-processing, pressure-flow proxy analysis, publication-style plots, and CFD contour/profile visualization.
Archived versions:
- v0.1.0: https://github.com/p26412/ThermoFOAM-DC/tree/v0.1.0
- v0.2.0: https://github.com/p26412/ThermoFOAM-DC/tree/v0.2.0
## v0.2 scope
Included in this release:
- simplified 3D data-center room with floor supply tiles, ceiling return, and six rack heat-source zones
- OpenFOAM Foundation v13 / `foamRun -solver fluid` style case setup
- RNG k-epsilon primary RANS workflow
- v0.1 grid, y+, and turbulence-model sensitivity documentation retained
- ten-case v0.2 parameter-study matrix
- automated case generator for C00-C09
- custom `dcMetricsPlus` post-processing utility
- global late-window tables and SVG plots
- optional per-rack table and heatmap generation from `dcMetricsPlus_perRack` outputs
- ParaView Python CFD figure generation
- filled contours with optional isolines
- line-profile CSV/SVG generation for `Ux`, `Uy`, `Uz`, `|U|`, `T`, `p_rgh`, `p`, `k`, `epsilon`, `omega`, `nut`, and `alphat` when available
---
## v0.2 case matrix
| Case | Folder | Description |
|---|---|---|
| C00 | `C00_baseline` | Six racks at 3 kW each, supply velocity 0.75 m/s, supply temperature 291 K |
| C01 | `C01_lowSupplyVelocity` | Baseline heat load, lower supply velocity 0.50 m/s |
| C02 | `C02_highSupplyVelocity` | Baseline heat load, higher supply velocity 1.00 m/s |
| C03 | `C03_warmerSupplyAir` | Baseline heat load, warmer supply temperature 295 K |
| C04 | `C04_highRackLoad` | All racks increased to 5 kW each |
| C05 | `C05_overloadedRack_L2` | Rack L2 overloaded to 8 kW, other racks at 3 kW |
| C06 | `C06_worstCase_lowFlow_highLoad` | Low flow with all racks at 5 kW |
| C07 | `C07_mitigation_highFlow_highLoad` | High-flow mitigation for all racks at 5 kW |
| C08 | `C08_overloadedRack_L2_lowFlow` | Overloaded L2 with low supply velocity |
| C09 | `C09_overloadedRack_L2_highFlow` | Overloaded L2 with high supply velocity |
The machine-readable case matrix is stored in:
```text
metadata/v02_case_matrix.csv
>>>>>>> aeb3467 (Release ThermoFOAM-DC v0.2 ten-case parameter-study workflow)<<<<<<< HEAD
cases/ OpenFOAM case setups
src/ dcMetricsPlus source code
scripts/ grid, metrics, plotting, v0.2 case generation, and y+ helper scripts
docs/ methodology and publication notes
results/ curated CSV tables and plots
environment/ OpenFOAM version/run notes
ThermoFOAM-DC/ cases/ 01_baseline_RNGkEpsilon/ 02_baseline_kEpsilon_sensitivity/ 03_baseline_kOmegaSST_sensitivity/ parameterstudy/ C00_baseline/ C01_lowSupplyVelocity/ ... C09_overloadedRack_L2_highFlow/ scripts/ create_parameter_cases_v02_10cases.py collect_per_rack_summary.py run_v02_analysis.sh v02_generate_tables_and_plots.py cfd_viz/ src/ dcMetricsPlus/ metadata/ v02_case_matrix.csv inputs/ README.md docs/ results/ tables/ plots/
Generated OpenFOAM time folders, `processor*` folders, logs, VTK output, ParaView `.foam` files, and build outputs are excluded by `.gitignore`.
---
## Requirements
Core CFD workflow:
```text
OpenFOAM Foundation v13 or compatible openfoam-dev style setup
Python 3
Optional visualization workflow:
ParaView with pvpython, or python3-paraview
The table and SVG-plot scripts intentionally avoid NumPy, pandas, and matplotlib so that summary generation works on minimal HPC environments.
From the repository root:
source /opt/openfoam13/etc/bashrc
cd src/dcMetricsPlus
wmake
cd ../..Adjust the OpenFOAM path if your installation is different.
The release already includes generated C00-C09 case templates under cases/parameterstudy. To regenerate them from a baseline case:
python3 scripts/create_parameter_cases_v02_10cases.py \
cases/01_baseline_RNGkEpsilon \
cases/parameterstudy \
--overwriteFor the full v0.2 sweep, the recommended production mesh is the grid-10 case from the v0.1 mesh study. If you have regenerated gridStudy_RNG/grid_10, use it as the base:
python3 scripts/create_parameter_cases_v02_10cases.py \
gridStudy_RNG/grid_10 \
cases/parameterstudy \
--overwriteFrom the repository root:
source /opt/openfoam13/etc/bashrc
./Allrun cases/parameterstudyEquivalent manual loop:
cd cases/parameterstudy
for case in C*/; do
echo "Running $case"
( cd "$case" && ./Allclean && ./Allrun )
done
cd ../..If the simulations are already complete and you already have:
postProcessing/dcMetricsPlus/0
postProcessing/dcMetricsPlus/1000
...
postProcessing/dcMetricsPlus/8000
then you do not need to rerun dcMetricsPlus.
To recompute global metrics over all saved times:
cd cases/parameterstudy
for case in C*/; do
echo "Metrics $case"
( cd "$case" && dcMetricsPlus -time '0:8000' )
done
cd ../..If your custom utility also writes per-rack metrics to:
postProcessing/dcMetricsPlus_perRack/<rack>/<time>/metrics.csv
then the v0.2 analysis wrapper can automatically collect those into inputs/v02_per_rack_summary_user.csv.
Use a late-window average to avoid startup transient contamination:
bash scripts/run_v02_analysis.sh \
--cases-root cases/parameterstudy \
--late-start 4000Expected global outputs:
results/tables/v02_global_timeseries.csv
results/tables/v02_global_summary.csv
results/tables/v02_global_summary_compact.csv
results/tables/v02_flow_balance_table.csv
results/tables/v02_heat_balance_diagnostic_table.csv
results/tables/v02_main_findings.csv
results/plots/publication/Fig02_TavgRackInlet_mean_std.svg
results/plots/publication/Fig03_T95RackInlet_mean_std.svg
results/plots/publication/Fig04_rackRiskFraction_mean_std.svg
results/plots/publication/Fig05_roomHotspotFraction_mean_std.svg
results/plots/publication/Fig06_pressureFlowProxy_mean_std.svg
results/plots/publication/Fig07_pressureProxy_vs_T95RackInlet.svg
If per-rack data are available, additional outputs include:
results/tables/v02_per_rack_summary.csv
results/tables/v02_per_rack_hotspot_ranking.csv
results/plots/publication/Fig08_perRack_Tavg_heatmap.svg
results/plots/publication/Fig09_perRack_T95_heatmap.svg
results/plots/publication/Fig12_perRack_risk_heatmap.svg
A root-level helper is also provided:
./Allpostprocess_v02 cases/parameterstudy 4000Create .foam files:
bash scripts/cfd_viz/make_foam_files.sh cases/parameterstudyGenerate optional derived CFD fields at time 8000:
source /opt/openfoam13/etc/bashrc
bash scripts/cfd_viz/write_cfd_fields_all_cases.sh cases/parameterstudy 8000Generate main ParaView CFD figures:
export PVPYTHON_BIN=pvpython
bash scripts/cfd_viz/run_pv_figures_all_cases.sh cases/parameterstudy 8000Generate velocity/scalar contours with contour lines and profile plots:
export PVPYTHON_BIN=pvpython
PV_NUM_CONTOUR_LINES=18 PV_CONTOUR_LINE_WIDTH=1.5 \
bash scripts/cfd_viz/run_velocity_figures_all_cases.sh \
cases/parameterstudy \
8000 \
results/plots/cfd_velocity_with_isolinesThis produces filled contours, isolines, and profile plots for available fields such as:
Ux, Uy, Uz, |U|, T, p_rgh, p, k, epsilon, omega, nut, alphat
aeb3467 (Release ThermoFOAM-DC v0.2 ten-case parameter-study workflow)
- racks are represented as heat-source zones, not detailed server cabinets <<<<<<< HEAD
- no porous rack resistance in v0.1
- no experimental validation yet
- transient RANS was tested but was too expensive for this v0.1 workflow
- LES/hybrid RANS-LES are deferred to later high-fidelity work
Add RNG k-epsilon design parameter studies:
- low supply velocity
- high supply velocity
- warmer supply air
- higher rack heat load
- one overloaded rack
- optional worst-case and mitigation cases
Add porous rack resistance and better rack airflow representation.
Add validation or benchmark comparison with published data-center cooling datasets.
- no porous rack pressure-loss model in v0.2
- no experimentally validated data-center benchmark comparison yet
- pressure-flow proxy is a relative engineering metric, not a full fan-energy model
- per-rack post-processing depends on the availability of
dcMetricsPlus_perRackoutputs - CHT, server fan curves, CRAH/CRAC coil models, and raised-floor plenum modelling are deferred
v0.2 is suitable as a GitHub engineering/research workflow showing:
- reproducible OpenFOAM case setup
- parametric CFD case generation
- automated hotspot metrics
- late-window statistical reporting
- per-rack hotspot comparison when available
- CFD visualization and line-profile extraction
For journal submission, v0.2 should be extended with validation, uncertainty analysis, selected fine-grid reruns, and improved physical realism.
GPL-3.0-or-later.
aeb3467 (Release ThermoFOAM-DC v0.2 ten-case parameter-study workflow)